1. Regularly check the terminal voltage and internal resistance of each unit battery. For the 12V unit battery, if it is found that the terminal voltage difference between each unit cell exceeds 0.4V or the internal resistance of the battery exceeds 80mΩ, the unit battery should be balancedly charged to restore the internal resistance of the battery. And eliminate the terminal voltage imbalance between each unit cell. When the charging is balanced, the charging voltage can be 13.5 to 13.8V. Most of the batteries that have been well-balanced and charged can restore their internal resistance to less than 30mΩ.
During the operation of the UPS power supply, the above imbalance caused by the characteristics of each unit battery changes with time is impossible to eliminate by relying on the internal charging circuit of the UPS power supply. Therefore, a battery having a significant imbalance in such characteristics has occurred. If the group does not take offline equalization processing in time, its imbalance will become more and more serious.
2. Re-float, the UPS power supply is shut down for more than 10 days. Before restarting, the UPS power supply should be started under the condition of no load to re-charge the battery for 10~12h or more with the charging circuit inside the machine.
The UPS power supply is in a floating state for a long time without a discharge process, which is equivalent to being in a "storage standby" state. If this state lasts for a long time, the battery will be scrapped due to "storage for too long". It mainly shows that the internal resistance of the battery increases, and the internal resistance can reach several Ω in severe cases.
We found that at room temperature 20 ° C, after storage for 1 month, the capacity of the battery is about 97% of its rated value. If it is stored for 6 months, its usable capacity becomes 80% of the rated capacity. If the storage temperature rises, its usable capacity will also decrease.
Therefore, it is recommended that the user intentionally unplug the mains input every 20 °C months to allow the UPS to operate in a state where the battery supplies energy to the inverter. However, this operation is not suitable for a long time. When the load is about 30% of the rated output, it can be discharged for about 10 minutes.
3. Reduce the deep discharge, the service life of the battery is closely related to the depth of its discharge. The lighter the load on the UPS power supply, the greater the ratio of the available capacity and its rated capacity when the mains supply is interrupted. In this case, when the UPS power supply is automatically shut down due to the low battery voltage, the battery is The depth of discharge is deeper.
How does the actual process reduce the battery's deep discharge? The method is very simple: when the UPS power supply is interrupted by the mains supply and the battery is supplied to the inverter, most of the UPS power will sound a periodic alarm sound with a gap of about 4s to inform the user that the battery is now powered by the battery. . When the alarm sounds suddenly, it indicates that the power supply is in deep discharge, and emergency treatment should be performed immediately to turn off the UPS power. It is not forced to do so, generally do not let the UPS power supply work until the battery voltage is too low and automatically shut down.
4, the use of power supply peak charging, for the UPS power supply for a long time in the market low-voltage power supply or frequent power outages, in order to prevent premature damage to the battery due to long-term charging, you should make full use of the peak power supply (such as late night time) to charge the battery To ensure that the battery has enough charging time after each discharge. After the battery is deeply discharged, it takes at least 10 to 12 hours to recharge to 90% of the rated capacity.
5, pay attention to the choice of charger. Maintenance-free sealed batteries for UPS power supplies cannot be charged with a thyristor-type "quick charger". This is because the charger will cause the battery to be in a state of both "instantaneous overcurrent charging" and "instantaneous overvoltage charging." This state will greatly reduce the battery's usable capacity, which will cause the battery to be scrapped. When using the UPS power supply of the constant voltage cut-off charging circuit, be careful not to set the battery voltage too low to protect the operating point too low. Otherwise, it will easily generate overcurrent charging at the beginning of charging. Of course, it is better to have both constant current. There is also a constant voltage charger to charge it.
6, to ensure the power supply ambient temperature. The capacity available for the battery is closely related to the ambient temperature. Under normal circumstances, the performance parameters of the battery are calibrated at room temperature of 20 ° C. When the temperature is lower than 20 ° C, the available capacity of the battery will be reduced, and when the temperature is higher than 20 ° C, it is available. The capacity used will increase slightly. Different types of batteries from different manufacturers are affected by temperature. According to statistics, at -20 °C, the available capacity of the battery can only reach about 60% of the nominal capacity. It can be seen that the influence of temperature cannot be ignored.
Of course, to extend the life of the battery pack should not only pay attention to maintenance and use, but also should consider the load characteristics (resistance, inductance, capacitance) and size when selecting. Do not leave the battery in an excessively light load for a long time, so as to prevent the battery from being discharged due to the battery discharge current being too small.
Motorcycle Parts Motorcycle Cap
[QUALITY ASSURANCE]Our motorcycle Ignition Switch fuel air cap lock is made of high quality stainless steel. The material is waterproof, wearresistant, antioxidation, durable and suitable for longterm use.
[QUALITY ASSURANCE]Our motorcycle ignition switch fuel air cap lock is made of high quality stainless steel. The material is waterproof, wear-resistant, anti-oxidation, durable and suitable for long-term use.
[HIGHPERFORMANCE]Antirust, exquisite design, locking function can fix the engine oil tank and prevent its vibration when driving or turning. Fast and flexible locking and unlocking improves safety and efficiency in harsher conditions.
[PRECISION MATERIALS]Strict quality control standards ensure long service life and optimal operation. Precision manufacturing to ensure high sensitivity, fast response and easy control. Manufactured to meet the expectations of fit, shape and function.
[STRICT QUALITY CONTROL]The quality of our products is highquality. reliable use of international standards. Compared with other similar products, our products have higher performance, you can use them with confidence and bring you a perfect shopping experience
[INTERNATIONAL STANDARD]The production of our products strictly follows international standards and strives for perfection at every step. Fine sanding makes the texture smoother and provides a comfortable operating feeling. Every detail of us is a shopping experience for your satisfaction
Tank Cap,Motorcycle Cap,Fuel Filter Cap,Motorcycle Fuel Cap
Zhejiang Zhengdong Motorcycle Parts Co., Ltd. , https://www.zhengdonglock.com